PS69-DPS ♦ CompactLogix or MicroLogix Platform

Reference

Profibus DP Slave Communication Module

User Manual

ProSoft Technology, Inc.

Page 87 of 108

May 9, 2014

Supported PROFIBUS-DP Messages

The CompactLogix Slave module supports the following message functions.

Service

Cmd Code

Group

Description

DPS Diagnostic Request

24

This service enables the user to send a single diagnostics
request to a Master.

DPV1 Class 1 Read Response

17

DPV1

With this service, the Slave module can respond to a DPV1
Read Request from the PROFIBUS Master. This service
works by utilizing the Master address, Data size, Slot and
Index indicated within the DPV1 Status Registers.

DPV1 Class 1 Write Response

17

DPV1

With this service, the Slave module can respond to a DPV1
Write Request from the PROFIBUS Master. . This service
works by utilizing the Master address, Data size, Slot and

Index indicated within the DPV1 Status Registers.

DPV1 Class 1 Alarm Request

18

DPV1

This service is used to send a DPV1 Alarm Request
message to a PROFIBUS Master.

Note: The sample project includes an example for each of these services.

Standard Messaging

The sections below contain the descriptions of the Standard Message supported
by the PROFIBUS Slave module.

DPS Diagnostic Request
The Diagnostic Request command can be used by the controller user application
to generate a single diagnostic request to a Master. The MSG instruction
Request/Confirmation format is as follows.