5.1.3 Functional Specifications

Specification

Description

Input data

max. 244 Bytes

Output data

max. 244 Bytes

DPV1 services

Read / Write class 1, Alarm

GSD file

PSFT097A.gsd

Up to 32 PROFIBUS devices can be connected to one bus segment. If several
bus segments are linked to each other with repeaters, there can be up to 127
devices on the network.

The maximum length of a bus segment depends on the baud rate used. Only
PROFIBUS certified cable, preferably Belden 3079A cable (or equivalent), should
be used.

Baud rate in kBit/s

Max. Distance

9.6

1,200 m / 4000 ft

19.2

1,200 m / 4000 ft

93.75

1,200 m / 4000 ft

187.5

1,000 m / 3280 ft

500

400 m / 1300 ft

1,500

200 m / 650 ft

3,000

100 m / 325 ft

6,000

100 m / 325 ft

12,000

100 m / 325 ft

Parameter

Value

Impedance

135 to 65 Ohm

Capacity

< 30 pF/m

Loop resistance

110 Ohm/km

Wire gauge

0.64 mm

Product Comparison

MVI69-PDPS

PS69-DPS

Cross-platform similarity

X

X

PROSOFT.fdt network configuration

X

X

Cyclic I/O (words)

200 in/
200 out

244 in/
244 out

FDT communication support (serial only) X

X

PROFIBUS PNO Certified

X

PROFIBUS DPV1 Support (Acyclic
messages, Acyclic Read/Write Data)

X

Price/Performance for OEM & Machine
Builders

X

RSLogix 5000 configuration

X

CIP Messaging (better performance,
ladder communication)

X

Lower Cost

X

Advertising