ProSoft Technology PS69-DPS User Manual

Page 80

Advertising
background image

Reference

PS69-DPS ♦ CompactLogix or MicroLogix Platform

User Manual

Profibus DP Slave Communication Module

Page 80 of 108

ProSoft Technology, Inc.

May 9, 2014

DPV1 Status Registers
The controller application program will use the DPV1 status registers as an
indication that the network Master has sent an unsolicited DPV1 Read/Write
request. The first will contain two bits which indicate if a read or write needs to be
processed. If this register contains a non-

zero value, the Slave’s user program

must create an appropriate response to this request by using a CIP MSG
command (shown in messaging section). The following table contains the
mapping of these registers.

Byte Offset

Structure Member Data Type

Data Type

Description

32

RWInd

SINT

Read/Write
Indication

A Read/Write Request has been received

33

RWIndCnt

SINT

Read Write
Indication Counter

Increments on every new DPV1 request

34

MaAdr

SINT

Master Address

Address of Requesting Master

35

Slot

SINT

Slot number

Requested Slot Number

36

Index

SINT

Index

Requested Index

37

DataLen

SINT

Date Length

Requested Data Length

RWInd := DPV1 Read/Write Indication Status Bits

Bit Offset

Structure Member Data Type

Description

0

ReadReq

BOOL

1 = Indicates a Read Request

1

WriteReq

BOOL

1 = Indicates a Write Request

2

Reserved

BOOL

Reserved

3

Reserved

BOOL

Reserved

4

Reserved

BOOL

Reserved

5

Reserved

BOOL

Reserved

6

Reserved

BOOL

Reserved

7

Reserved

BOOL

Reserved

Note: Every DPV1 read or write request must be acknowledged by the PLC application program.

Otherwise the PROFIBUS master shuts down communication for both channels, V0 (cyclic IO
data) and V1 (non-cyclic messages). This can cause unexpected lost of data between the master

and the PS69-DPS slave.

Extended Status Information
Via the extended status area the Slave module is in the position to transfer 96
Byte extended status information to the controller application. The information
transferred depends on the parameter "ExtStaSelect" in the "Device Command
Register". This can be controlled by the application program. If the controller
application selects a specific extended status, it will be acknowledged by the
Slave module in the status region in "ExtStaSelect". If the slave adapter does not
acknowledge this selection, the extended information is invalid. The number of
bytes within the extended status area which are valid depends on the selected
status. The number of valid bytes will be shown in the status area in "ExtStaLen".