Viewing i/o file data, Viewing version information, Warm booting the module – ProSoft Technology MVI46-MBP User Manual

Page 26

Advertising
background image

MVI46-MBP ♦ SLC Platform

Diagnostics and Troubleshooting

Modbus Plus Communication Module

Page 26 of 101

ProSoft Technology, Inc.

February 19, 2008

Viewing I/O File Data

Press [O] to display the module's global input and output data.

The In File Address Map, values represent the data set for selecting the
registers in the module's database to transfer to the In File Data area. The In File
Data

section displays the current values transferred from the module to the SLC

processor. The Out File Data section contains the values used for Global Output
Data to be transferred from the module to the Modbus Plus network.

Viewing Version Information

Press [V] to view Version information for the module.

Use this command to view the current version of the software for the module, as
well as other important values. You may be asked to provide this information
when calling for technical support on the product.

Values at the bottom of the display are important in determining module
operation. The Program Scan Counter value is incremented each time a
module's program cycle is complete.

Tip: Repeat this command at one-second intervals to determine the frequency of program
execution.

Warm Booting the Module

Caution: Some of the commands available to you from this menu are designed for advanced
debugging and system testing only, and can cause the module to stop communicating with the
processor or with other devices, resulting in potential data loss or other failures. Only use these
commands if you are specifically directed to do so by ProSoft Technology Technical Support staff.
Some of these command keys are not listed on the menu, but are active nevertheless. Please be
careful when pressing keys so that you do not accidentally execute an unwanted command.

Press [W] from the Main Menu to warm boot (restart) the module. This command
will cause the program to exit and reload, refreshing configuration parameters
that must be set on program initialization. Only use this command if you must
force the module to re-boot.

Advertising
This manual is related to the following products: