Execution status can be monitored in the same fashion as other commands in
the Master Command List, via the Master Command Status block.

Successful Execution

If the command was successful (Status Code = 0x01), the status will be
maintained as long as the Event Command bit is set. After the enable bit is
cleared, the Status Code field will go to zero (0).

Unsuccessful Execution

If the command was unsuccessful (Status Code > 0x01), the status will be
maintained until the command executes successfully. The ladder logic must 're-
submit' the command (clear the enable bit and set it again) in order for the
command to execute again.

5.2.4 Dual

Port

Operation

Some Modbus Plus modules are equipped with a second, redundant Modbus
Plus port. A Dual Port Modbus Plus network is implemented in the following way:
ƒ

The primary network connects to Port 1 on all modules.

ƒ

The secondary (backup) network connects to Port 2 on all modules.

If the primary network connected through Port 1 fails (for example, if a cable is
cut or disconnected), the network connected through Port 2 will become active,
maintaining the connection between devices.

Important: All Modbus Plus nodes on a network must be equipped with dual ports in order to
implement redundant port operation.