Modbus plus communication port, Database definition, Module memory map – ProSoft Technology MVI46-MBP User Manual

Page 60: Overview, Database, Definition, 6 modbus plus communication port, 7 database definition

Advertising
background image

MVI46-MBP ♦ SLC Platform

Reference

Modbus Plus Communication Module

Page 60 of 101

ProSoft Technology, Inc.

February 19, 2008

5.6

Modbus Plus Communication Port

The MVI46-MBP module has two physical Modbus Plus connectors with two DB-
9 Female plugs located on the front of the module.

5.7 Database

Definition

This section contains a listing of the internal database of the MVI46-MBP
module. This information can be used to interface other devices to the data
contained in the module.

5.7.1 Module Memory Map

Overview

Access

Module Address
Range

Modbus Address
Range

Description Block

Low

High

Low

High

Size

R/W 0

3999 40001

44000 Data

Registers

4000

R

4000

4069

44001

44070

Global In Update Status

70

R

4070

4269

44071

44270

Master Command Status

200

R

4270

4299

44271

44300

Misc Module Status

30

R

4300

4369

44301

44370

Global In Update Counters

70

R/W

4370

4409

44371

44410

Module Configuration Block

40

R/W

4410

4449

44411

44450

Global In File Map

40

R/W 4450 5089 44451

45090 Device

Definition

640

R/W

5090

7089

45091

47090

Master Command List

2000

O File

7090

7129

47091

47130

Global Out Image

40

I File

7130

7169

47131

47170

Global In Image

40

R

7170

7221

47171

47222

Command Event Data

52

The Data Registers area holds data collected from other nodes on the network
(master read commands or global input data) or data received from the
processor (write blocks). Additionally, this data area is used as a data source for
the processor (read blocks) or other nodes on the network (master write
commands).

Advertising