ProSoft Technology MVI46-MBP User Manual

Page 73

Advertising
background image

Reference MVI46-MBP

♦ SLC Platform

Modbus Plus Communication Module

ProSoft Technology, Inc.

Page 73 of 101

February 19, 2008

DB
Address

Modbus
Address

Parameter Description

5090 45091 Enable

This parameter is used define if the command will
be executed or will be disregarded. The following
values are valid: 0=Disables the command and it
will not execute; 1=The command will be
considered for execution each scan of the
command list and will be controlled by the PollInt
parameter; and 2=The command will only execute
if the event control bit for the command is set.

5091 45092 Module's

Database
Register Number

This parameter specifies the starting internal
register address to be associated with the
command. Valid entry for this parameter is 0 to
3999.

5092 45093 Polling

Interval

This parameter defines the minimum number of
seconds to wait between the execution of
continuous commands (Enable=1). This poll
interval command can be used to lighten the
communications load on a busy network. Valid
entry for this parameter is 0 to 65535.

5093 45094 Register

Count

This parameter defines the number of registers to
be considered by the command. Valid entry for
this parameter is 1 to 100.

5094 45095 Swap

Code This parameter is not implemented in the current

version of the software but will be used in the
future to swap the bytes of word and double-word
values when floating-point data is required.

5095 45096 Device

Index This parameter associates the command with a

device defined in the device definition table
(Device[ ] in the MBPlusModuleDef object). The
index defined in this parameter sets the route path
defined for the device in the Modbus Plus
message.

5096 45097 Function

Code

This parameter specifies the function to be
performed by the command. Valid entries are 3=
Read register data from a node and 16= Write
register data to a node.

5097 45098 Register Address

in Device

This parameter defines the starting address in the
device being considered by the command. Values
entered in this field are dependent on the node's
database definition. Refer to the specific
manufacture's database definition for the device to
determine the location of the data to be interfaced.

5098 45099 Spare

Not

used

5099 45100 Spare

Not

used