Error code definition, Miscellaneous module status – ProSoft Technology MVI46-MBP User Manual

Page 63

Advertising
background image

Reference MVI46-MBP

♦ SLC Platform

Modbus Plus Communication Module

ProSoft Technology, Inc.

Page 63 of 101

February 19, 2008

Error Code Definition

High Byte

Low Byte

Description

0x00

0x00

Normal - Driver will reset when processing command

0x01

Command has completed successfully

0x02

Routing

Errors

0x01

No response received - Is addressed unit online

0x02

program access denied

0x04

exception response received

0x08

invalid node type in routing path

0x10

slave rejected the Modbus command - invalid input path??

0x20

initiated transaction forgotten by slave

0x40

unexpected master output path received

0x80

unexpected response received

0x04

Configuration

Errors

0x01

Invalid Configuration for Command

0x02

Invalid Command Type - 1 = Write, 2 = Read , All other error

0x04

0x08

0x10

0x20

0x40

0x80

Miscellaneous Module Status

Element DB

Address

Description

0

4270

Module Status - Software Reset Response

1 4271

Peer

Status

2

4272

Token Pass Counter

3

4273

Token Rotation Time in milliseconds

4 4274-H

Communication

Failed Error Counter

4

4274-L

Communication Retry Counter

5

4275-H

No Response Received Error Counter

5

4275-L

Good Received Packet Success Counter

6

4276-H

Unexpected Path Error Counter

6

4276-L

Exception Response Received Error Counter

7

4277

Data master output path 1 & 2 counter

8

4278

Data master output path 3 & 4 counter

9

4279

Data master output path 5 & 6 counter

10

4280

Data master output path 7 & 8 counter

11

4281

Data slave output path 1 & 2 counter

12

4282

Data slave output path 3 & 4 counter

13

4283

Data slave output path 5 & 6 counter

14

4284

Data slave output path 7 & 8 counter

15

4285

Global Out Update Status

16

4286

Global Out Update Counter

17

4287

Data transfer read counter

Advertising