Peer status codes, Global out update status, Global in update counters – ProSoft Technology MVI46-MBP User Manual

Page 65

Advertising
background image

Reference MVI46-MBP

♦ SLC Platform

Modbus Plus Communication Module

ProSoft Technology, Inc.

Page 65 of 101

February 19, 2008

Code Description
0X8E

Transmit OK MAC state

0X8F

No receive buffer free

0X90

Bad input transfer length

0X91

Reserved rev buffer error

0X92

Bad trans control state

0X93

Bad word request bit

0X94

Node queue overflow

0X95

Bad data queue error

0X96

Empty data path error

0X97

Bad path search index

0X98

Bad data slave path

Peer Status Codes

Code Description
0

Monitor link operation

32

Normal link operation

64

Never getting token

96 Sole

station

128 Duplicate

station

Global Out Update Status

Code Description
0x01 Updating

all

OK

0x02 Not

assigned

0x04 Not

assigned

0x08

Global update timeout (not transmitted in 500 milliseconds)

0x10

Global data not configured (length set to zero)

0x20 Not

assigned

0x40

Invalid Global Data Length (Length > 32 words)

0x80 Not

assigned

Global In Update Counters

Element DB

Address

Description

0

4300

Global In Update Counter - Device #1

1

4301

Global In Update Counter - Device #2

2

4302

Global In Update Counter - Device #3

3

4303

Global In Update Counter - Device #4

4

4304

Global In Update Counter - Device #5

5

4305

Global In Update Counter - Device #6

6

4306

Global In Update Counter - Device #7

7

4307

Global In Update Counter - Device #8

8

4308

Global In Update Counter - Device #9

9

4309

Global In Update Counter - Device #10

10

4310

Global In Update Counter - Device #11

- - -

- - -

- - -

60

4360

Global In Update Counter - Device #61