MITSUBISHI ELECTRIC 700 Series User Manual

Page 24

Advertising
background image

19

Device Map

1

P

L

C

FU

N

C

TI

O

N

D

e

vi

ce

M

a

p

Number

Name

Description

Page

S

p

eci

a

l r

egi

st

e

rs

fo

r con

tr

ol

D9234

Second

parameter

changing (RAM) When setting the calibration(bias/gain) parameters.

H00: Frequency(toruque)

H01: Parameter-set analog value

H02: Analog value input from terminal

34, 36

D9235

Second

parameter

changing

(EEPROM)

D9236

Pulse train input

sampling pulse

The number of pulses counted in count cycle is

stored. (0 to 32767)

40

D9237

Pulse train input

cumulative count

value L

The cumulative value of the number of sampling

pulses is stored. (0 to 99999999)

D9238

Pulse train input

cumulative count

value H

D9239

Reset request of

pulse train input

count

The sampling pulses and cumulative count value are

cleared. Automatically changes to "0" after reset.

(1: count clear)

D9240

Count start of the

pulse train input

Start counting the sampling pulses and cumulative

count value. (0: count stop, 1: count start)

D9241

Parameter

number (RAM)

Set the number of parameter read or written of the

inverter.

34, 36

D9242

Parameter

description

(RAM)

The parameter description of the inverter (RAM value)

specified by D9241 is stored. Set the parameter

setting for parameter write.

D9243

Parameter

number

(EEPROM)

Set the number of parameter read or written of the

inverter.

D9244

Parameter

description

(EEPROM)

The parameter description of the inverter (EEPROM

value) specified by D9243 is stored. Set the

parameter setting for parameter write.

D9245

Terminal 1 input

Analog input value of terminal 1 (0.1% increments) is

stored.

39

D9246

Terminal 2 input

Analog input value of terminal 2 (0.1% increments) is

stored.

D9247

Terminal 4 input

Analog input value of terminal 4 (0.1% increments) is

stored.

D9248

PID set point /

PID deviation

Set the PID set point or PID deviation (0.01% units)

41

D9249

PID

measurement

value

Set the PID measurement value (0.01% units)

D9250

PID manipulated

variable

Stores the PID manipulated variable (0.01% units)

D9251

Terminal FM

output

When Pr. 54 is set to "70", pulse train can be output

from terminal FM. High speed pulse train output can

be performed. (0.1% increments)

39

D9252

Terminal AM

output

When Pr. 158 is set to "70", analog output can be

performed from terminal AM. (0.1% increments)

D9253

AM0 output

Analog output can be performed from terminal AM0

and AM1 of the FR-A7AY. (0.1% increments)

D9254

AM1 output

D9255

PID operation

control

Setting 1 starts PID control.

41