MITSUBISHI ELECTRIC 700 Series User Manual

Page 35

Advertising
background image

30

Inverter Status Monitoring, Special Registers
for Control

(5) Parameter clear (D9147)

Writing H9696 or H9966 to D9147 clears all parameters. Writing H5A5A or
H55AA to D9147 clears the parameters other than the communication
parameters (Refer to the Inverter instruction manual (applied)).

At completion of clear, the write completion signal (X27) turns on, and at the
same time, 0 is set to D9150. If any value outside the setting range is written or
write is performed during inverter operation, HFFFF is set to D9150 as soon as
the write completion signal (X27) turns on, resulting in abnormal completion. If
abnormal completion occurs, the parameters are not cleared.

<All parameter clear program example>
The following program clears all parameters.

Device No.

Setting

Description

Details

D9147

H9696

All parameter clear

Terminal functions are not
cleared.

H9966

Terminal functions are
cleared.

H5A5A

Parameters other than
communication parameters
are cleared.

Terminal functions are not
cleared.

H55AA

Terminal functions are
cleared.

REMARKS

Check the terminal function parameters and communication-related parameters in the
parameter list (Refer to the Inverter instruction manual (applied)).

POINT

Setting is enabled in the PU operation mode and NET operation mode. Refer to
the inverter instruction manual (applied).

‹

Related device‹

Device D9150: Parameter access error code (refer to page 33)

Normal write

Abnormal write

Stores H9696 (all parameter

clear code) to D9146 and turns

on alarm definition batch clear

command.

(Until completion signal turns on)

All parameter clear request

Turns on all parameter

clear request pulse.

Check whether all parameter

clear signal turned on to judge

whether write was performed

normally or not.