CC-Link I/O Specifications

2

CC-

L

in

k CO

M

M

UNICAT

ION

("n" indicates a value determined according to the station number setting.)
*1

Signal names are initial values. Using Pr. 180 to Pr. 186, Pr. 188, and Pr .189, you can

change input signal functions.

Signals of the RYn0, RYn1, and RYn9 can not be changed. Even when changed using Pr.

178, Pr. 179, and Pr. 187, the settings are invalid.

Refer to the inverter manual (applied) for details of Pr. 178 to Pr.189.

*2

Signal names are initial values. Using Pr. 190 to Pr .196, you can change output signal

functions.

Refer to the inverter manual (applied) for details of Pr. 190 to Pr.196.

(2) Remote resister

("n" indicates a value determined according to the station number setting.)

PLC function

device No.

Address

Description

PLC function

device No.

Address

Description

Upper 8

Bits

Lower 8

Bits

RWwn

Monitor

code 2

Monitor

code 1

RWrn

First monitor value

RWwn+1

Set frequency (0.01Hz

increments)

RWrn+1

Second monitor

value

RWwn+2

Link

parameter
expansion

setting

Instruction

code

RWrn+2

Reply

code2

Reply

code1

RWwn+3

Write data

RWrn+3

Read data

D9062

RWwn+4 Registers designed to

read data received
from the master
station

D9078

RWrn+4

Registers designed
to write data to be
sent to the master
station.

D9063

RWwn+5

D9079

RWrn+5

D9064

RWwn+6

D9080

RWrn+6

D9065

RWwn+7

D9081

RWrn+7