Data write timing chart – MITSUBISHI ELECTRIC 700 Series User Manual

Page 30

Advertising
background image

25

Inverter Status Monitoring, Special Registers

for Control

1

P

L

C

FU

N

C

TI

O

N

1.7.3

How to write data by controlling (OFF to ON) the write

command

You can write the operation mode and set frequency to the inverter, batch-clear the
alarm definitions, and clear all parameters.

The above data are written as soon as the write completion turns on after the write
command has turned from off to on.
(Alarm definition batch clear (D9146) and all parameter clear (D9147) turn on at
completion of clear.)
To write the data again, the write command must be turned off once, then on again.

Data write timing chart

Device

No.

Name

Write

Command

Write

Completion

Data Access

Enable Condition

D9143

Operation mode setting write

Y23

X23

Pr.79 =0, 2

D9144

Set frequency write (RAM)

Y24

X24

PU operation mode
(PU LED on) or CC-
Link operation mode
(PU and EXT LEDs
flicker slowly)

D9145

Set frequency write
(E

2

PROM)

Y25

X25

D9146

Alarm definition batch clear

Y26

X26

Always

D9147

All parameter clear

Y27

X27

As set in Pr. 77

X2n(n=3 to 7)
Write completion

D914n(n=3 to 7)
Write data

User data

Y2n(n=3 to 7)
Write command

1) In user sequence, user
data is stored into write
data area (D914n).

2) In user sequence, write
command is turned on.

4) After confirmation of write
completion, write command
is turned off.

3) Turns on when inverter CPU completes data

write to inverter.

Alarm definition clear and parameter

clear turn on at completion of clear.

0 written to D9150 indicates normal completion.

Any value other than 0 indicates abnormal completion.

5) Inverter CPU confirms that
write command is off and
turns off write completion.