1.7.4

Inverter operation status control

(1) Inverter operation status control (D9148)

Device for inverter operation status control. The operation of the inverter can be
controlled by turning on/off (1, 0) bits b0 to b11 of D9148.
All bits are factory-set to "0".

Example: When 5 is set to D9148, bits b0 and b2 are 1 (ON), and STF and RH

therefore turn on to give a high-speed forward rotation command.

Device No.

Name

Data Access Enable Condition

D9148

Inverter operation status control Always

Note that this function is enabled in
the external/NET operation mode.
(Not enabled in the PU
operation mode.)

D9149

Inverter operation status control

enable/disable

CAUTION

As in the external input terminals, functions can be assigned to the bits of

D9148 using Pr.178 to Pr.189. However, no function can be assigned to SQ

(sequence RUN setting: 50).

B15

B12B11

B8B7

B4B3

B0

0:OFF
1:ON

STF (Pr.178)
STR (Pr.179)
RH (Pr.182)
RM (Pr.181)
RL (Pr.180)
JOG (Pr.185)
RT (Pr.183)
AU (Pr.184)
CS (Pr.186)
MRS (Pr.187)
STOP (Pr.188)
RES (Pr.189)