32

Inverter Status Monitoring, Special Registers
for Control

(2) Inverter operation status control enable/disable setting (D9149)

You can enable or disable D9148 "inverter operation status control". The controls

of the corresponding bits of D9148 are enabled by turning on/off (1, 0) bits b0 to

b11 of D9149. All bits are factory-set to "0".

Example: When H1F is set to D9149, bits b0 to b11 are 1 (ON), the external terminal

inputs are therefore all disabled, and operation control using the inverter

operation status control (D9148) can be performed.

<Operation command setting program example>
The following program example runs the inverter at high speed in forward rotation

direction.

CAUTION

When D9148 "inverter operation status control" is enabled using D9149,

the control performed by external terminal inputs and the control

performed by CC-Link remote inputs are disabled for the enabled bits.

(Same as when "No functions" are set to Pr.178 to Pr.189.)

When the terminal is made valid from PLC function, control from external

terminal is made invalid.

B15

B12B11

B8B7

B4B3

B0

0:OFF
1:ON

STF (Pr.178)
STR (Pr.179)
RH (Pr.182)
RM (Pr.181)
RL (Pr.180)
JOG (Pr.185)
RT (Pr.183)
AU (Pr.184)
CS (Pr.186)
MRS (Pr.187)
STOP (Pr.188)
RES (Pr.189)

Invalid

1

1

1

1

1

1

1

1

1

1

1

1

Operation start

Operation stop

Turns on operation start pulse.

Enables all inverter operation status
control enable/disable bits, and
disables external terminal inputs.

Self-holds operation start, and turns
on bits 0 (STF) and 2 (RH) of inverter
operation status control, D9148.

At input of stop signal, clears inverter
operation status control, D9148,
to 0 and decelerates inverter to stop.

HFFF