MITSUBISHI ELECTRIC 700 Series User Manual

Page 59

Advertising
background image

54

CC-Link I/O Specifications

2.3.3

I/O signal when CC-Link Ver.2 quadruple setting is selected
(Pr. 544 = 114)

The device points usable in CC-Link communication are 32 input (RX) points (12
points are available for PLC function), 32 output (RY) points (12 points are available
for PLC function), 8 remote register (RWr) points and 8 remote register (RWw) points.

(1) Remote I/O

Same as when Pr. 544 = 112 (

Refer to page 52)

(2) Remote resister

("n" indicates a value determined according to the station number setting.)

PLC function

device No.

Address

Description

PLC function

device No.

Address

Description

Upper 8

Bits

Lower 8

Bits

RWwn

Monitor

code 2

Monitor

code 1

RWrn

First monitor value

RWwn+1

Set frequency (0.01Hz

increments)

RWrn+1

Second monitor

value

RWwn+2

Link

parameter
expansion

setting

Instruction

code

RWrn+2

Reply

code2

Reply

code1

RWwn+3

Write data

RWrn+3

Read data

RWwn+4

Monitor code 3

RWrn+4

Third monitor value

RWwn+5

Monitor code 4

RWrn+5

Fourth monitor value

RWwn+6

Monitor code 5

RWrn+6

Fifth monitor value

RWwn+7

Monitor code 6

RWrn+7

Sixth monitor value

D9062

RWwn+8

Registers designed to
read data received
from the master
station

D9078

RWrn+8

Registers designed
to write data to be
sent to the master
station.

D9063

RWwn+9

D9079

RWrn+9

D9064

RWwn+A

D9080

RWrn+A

D9065

RWwn+B

D9081

RWrn+B

D9066

RWwn+C

D9082

RWrn+C

D9067

RWwn+D

D9083

RWrn+D

D9068

RWwn+E

D9084

RWrn+E

D9069

RWwn+F

D9085

RWrn+F

Advertising