9 user area read/write method, 1 user parameter read/write method, User area read/write method – MITSUBISHI ELECTRIC 700 Series User Manual

Page 43: User parameter read/write method

Advertising
background image

38

User Area Read/Write Method

1.9 User Area Read/Write Method

Inverter parameters Pr.506 to Pr.515 can be used as user parameters.
Since this parameter area and the devices used with the PLC function, D110 to D119,

are accessible to each other, the values set in Pr.506 to Pr.515 can be used in a

sequence program. The result of operation performed in the sequence program can

also be monitored using Pr.506 to Pr.515.

1.9.1

User parameter read/write method

User parameter (Pr.506 to Pr.515) and device (D110 to D119) data can be read/written
freely. Data transfer between Pr.506 to Pr.515 and D110 to D119 is executed
automatically.
1) User parameter write processing

When values are written to Pr.506 to Pr.515 using the FR-PU04 or computer link

communication, they are written to the parameter storing RAM area and EEPROM

area, and further to D110 to D119 simultaneously.

2) User parameter read processing

When values are written to D110 to D119 from the PLC function side, they are

written to the parameter storing RAM area (Pr.506 to Pr.515) and read using the FR-

PU04/FR-PU07 or communication(RS-485 or communication option). (Since data

are not written to the EEPROM, making power-on reset returns the data to the

original values.)

3) Processing performed at inverter reset or power restoration

When the inverter is reset, the Pr.506 to Pr.515 values stored in the EEPROM are

transferred to the RAM area and D110 to D119.

Device

No.

Inverter

Parameter

No.

Name

Initial
Value

Setting

Range

Minimum Setting

Unit

Data Access

D110 to

D119

506 to 515

User

parameters

0

0 to

65535

1

Always

enabled

POINT

Example of using the user parameter area
When the timing is to be changed for machine adjustment using D110 that
stores the timer setting, setting Pr. 506 without modifying the program enters
the set data into D110, enabling adjustment.

Pr.506 to Pr.515

D110 to D119

Inverter parameters

PLC function devices

Pr.506 to Pr.515
(RAM)

D110 to D119

Pr.506 to Pr.515
(EEPROM)

3)

3)

1)

1)

2)

2)

1)

1)

FR-PU04 or RS-485
communication

Advertising