1.7.2

Data that are read by controlling (OFF to ON) the read

command

You can read the operation mode and set frequency of the inverter.

Data are stored into the above data devices as soon as the read completion turns from

off to on after the read command has turned from off to on.

If the read command remains on, data is not refreshed. (Data is not updated.)

Turn the device off once, then on again to refresh data.

Data read timing chart

(1) Operation mode setting read (D9140)

<Operation mode setting read program example>
The following program reads the operation mode data to D0.

Device

No.

Name

Read

Command

Write

Completion

Data Access

Enable Condition

D9140

Operation mode setting read

Y20

X20

Always

D9141

Set frequency read (RAM)

Y21

X21

D9142

Set frequency read (EEPROM)

Y22

X22

Data Setting

Operation Mode

H0000

NET operation mode

H0001

External operation mode

H0002

PU operation mode

REMARKS

When the Pr. 79 "operation mode selection" setting is other than "0", the operation mode is as
set. However, when Pr. 79 = "3" or "4", the operation mode is "H0002" (PU operation mode).

Read command

Read completion

Read data

User sequence
processing

1) Read command is turned
on in user sequence.

3) In user sequence, ON of read completion
is confirmed and data is read from special
register and processed.

4) After completion of read,
read command is turned off.

2) Inverter CPU stores inverter data
into special register and turns on
read completion.

5) Inverter CPU confirms that
read command is off and
turns off read completion.

Y2n(n=0 to 2)

X2n(n=0 to 2)

D914n(n=0 to 2)

Operation mode read setting request

Turns on operation mode

read request pulse.
Stores operation mode data to D0

when operation mode setting read

completion signal turns on.
Turns on operation mode setting

read command. (Until operation

mode setting read completion

signal turns on)