129

Sequence Instructions

3

SEQUENCE PRO

G

RAM

M

ING

3.25.7 Output Instructions : Leading edge, trailing edge

differential outputs ... PLS, PLF

Functions

(1) Turns the specified device on when the PLS command turns from OFF to ON,

and turns it off except when the PLS command turns from OFF to ON.

When there is one PLS instruction for the device specified at

during one scan,

the specified device turns on for one scan.
Do not execute the PLS instruction for the same device more than once during
one scan.

(2) If the status is switched to STOP and switched to RUN again after execution of

the PLS instruction, the PLS instruction is not executed.

Usable Devices

Digit

Designation

Error

Flag

Bit devices

Word (16-bit) devices

Constants

Level

X

Y

M

T

C

D

K

H

N

(M9010,

M9011)

{

{

PLS

D

PLS command

PLF command

Set data

Device number whose data
will be converted into pulses

D

D

1 scan

1 scan