20

Inverter Status Monitoring, Special Registers
for Control

1.7 Inverter Status Monitoring, Special Registers for Control

You can assign the data for grasping and changing the inverter's operation status to
D9133 - D9147 and read/write them from the user sequence. (Refer to page 14 for the
list.)

1.7.1

Data that can be read at all times

The following data can always be read. They are automatically refreshed every time
the END instruction is executed.

(1) Operation monitor

The following data devices are always read-enabled (write-disabled) to allow you to
monitor the output frequency, output current and output voltage of the inverter. Note
the setting units.

Device

No.

Name

Setting

Unit

Data Example

Data Access Enable

Condition

D9133

Output frequency
monitor

0.01Hz

Device data 6000

→ 60.00Hz

Always

D9134

Output current
monitor

0.01A

Device data 200

→ 2.00A

D9135

Output voltage
monitor

0.1V

Device data 1000

→ 100.0V

CAUTION

The frequency can be set in increments of 0.01Hz but actual operation is performed in
increments of 0.1Hz.