5 inverter parameter access error (d9150), 6 inverter status (d9151), Inverter parameter access error (d9150) – MITSUBISHI ELECTRIC 700 Series User Manual

Page 38: Inverter status (d9151)

Advertising
background image

33

Inverter Status Monitoring, Special Registers

for Control

1

P

L

C

FU

N

C

TI

O

N

1.7.5

Inverter parameter access error (D9150)

If any value outside the setting range is written during parameter write, set frequency
write, parameter clear, etc. from the sequence program of the inverter, or if write is
performed when write is disabled, a write alarm occurs and the corresponding alarm
code is stored into D9150.

<Parameter>

The parameter No. + H8000 is stored into D9150.
Example: If an error occurs during write of Pr.0 Torque boost, H8000 (H0 + H8000) is

stored into D9150.
If an error occurs during write of Pr.10 DC injection brake operation frequency,
H800A is stored into D9150.

<Operation mode, set frequency, alarm definition batch clear, all parameter

clear>

HFFFF is stored into D9150. (Normal 0)

1.7.6

Inverter status (D9151)

The running status and operating status of the inverter are stored.
The corresponding bits are set according to the inverter status.

Device No.

Name

Data Access Enable

Condition

D9150

Inverter parameter access error

Always

POINT

If write is completed normally after error occurrence, D9150 is not cleared
(D9150 data is held at error occurrence). When using D9150 to stop operation,
etc., the user must clear it.

Device No.

Name

Data Access Enable

Condition

D9151

Inverter status

Always

B15

B8B7

B4B3

B0

0:OFF
1:ON

Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency
detection(FU)
Alarm output(ALM)
Minor fault output(LF)

Advertising