1.13 Inverter Operation Lock Mode Setting

You can disable a sequence program from being executed until the sequence program
execution key is set to RUN (SQ signal is turned on).

POINT

When you want to perform only inverter operation without using the PLC function,
set "0" (inverter start signal enable) in this parameter.

Parameter

Name

initial

Setting

Setting

Range

Minimum Setting

Unit

415

Inverter operation
lock mode setting

0

0, 1

1

Setting

Description

0

The inverter start signal is made valid regardless of the sequence program
execution key.

1

The inverter start signal is made valid only when the sequence program
execution key is set to RUN (SQ signal is turned on).
When the sequence program execution key is in the STOP position (SQ
signal is off), the inverter does not start if the inverter start signal STF or STR
is turned on. (If the key is switched from RUN to STOP during inverter
operation, the inverter is decelerated to a stop.)

CAUTION

Independently of the Pr. 77 setting, this parameter value cannot be rewritten

during inverter operation.

During automatic operation performed using D9148(or M9200 to M9211) in the

sequence program, the inverter comes to a stop when the sequence is set to a

STOP status with "1" set in Pr.415. However, when "0" is set in Pr.415, the

device data are held and the operation status does not change if the sequence

is set to a STOP status. (Inverter operation is continued.)

REMARKS

This parameter setting is also valid for the start signal from the operation panel or FR-
PU04/FR-PU07.