3 cc-link i/o specifications, Cc-link i/o specifications – MITSUBISHI ELECTRIC 700 Series User Manual

Page 55

Advertising
background image

50

CC-Link I/O Specifications

2.3 CC-Link I/O Specifications

2.3.1

I/O signal when CC-Link Ver.1 one station is occupied
(Pr. 544 = 100)

The device points usable in CC-Link communication are 32 input (RX) points (16
points are available for PLC function), 32 output (RY) points (16 points are available
for PLC function), 4 remote register (RWr) points and 4 remote register (RWw) points.

(1) Remote I/O

PLC

function

device

No.

Remote

output
device

No.

Signal

PLC

function

device

No.

Remote

input

device

No.

Signal

X30

RYn0

Forward rotation command

X30

RXn0

Forward running

X31

RYn1

Reverse rotation command

X31

RXn1

Reverse running

X32

RYn2

High-speed operation

command

(terminal RH function) *1

X32

RXn2

Running

(terminal RUN function) *2

X33

RYn3

Middle-speed operation

command

(terminal RM function) *1

X33

RXn3

Up to frequency

(terminal SU function) *2

X34

RYn4

Low-speed operation

command

(terminal RL function) *1

X34

RXn4

Overload alarm

(terminal OL function) *2

X35

RYn5

Jog operation command

(terminal JOG function) *1

X35

RXn5

Instantaneous power failure

(terminal IPF function) *2

X36

RYn6

Second function selection

(terminal RT function) *1

X36

RXn6

Frequency detection

(terminal FU function) *2

X37

RYn7

Current input selection

(terminal AU function) *1

X37

RXn7

Error

(terminal ABC1 function) *2

X38

RYn8

Selection of automatic restart after

instantaneous power failure

(terminal CS function) *1

X38

RXn8

 (terminal ABC2 function) *2

X39

RYn9

Output stop

X39

RXn9

Pr. 313 assignment function

(DO0)

X3A

RYnA

Start self-holding selection

(terminal STOP function) *1

X3A

RXnA

Pr. 314 assignment function

(DO1)

X3B

RYnB

Reset

(terminal RES function) *1

X3B

RXnB

Pr. 315 assignment function

(DO2)

X3C

RYnC

General-purpose remote input

available in PLC function

X3C

RXnC

General-purpose remote input

available in PLC function

X3D

RYnD

X3D

RXnD

X3E

RYnE

X3E

RXnE

X3F

RYnF

X3F

RXnF

RY(n+1)0

to

RY(n+1)7

Reserved

RX(n+1)0

to

RX(n+1)7

Reserved

RY(n+1)8

Not used

(initial data process

completion flag)

RX(n+1)8

Not used

(initial data process request

flag)

RY(n+1)9

Not used

(initial data process request

flag)

RX(n+1)9

Not used

(initial data process

completion flag)

RY(n+1)A

Error reset request flag

RX(n+1)A

Error status flag

Advertising