SED2 VFD Electronic Bypass Option Operating Instructions

6

Siemens Building Technologies, Inc.

Contactors

The Controller board provides two or three relay contact circuits controlled by the
Electronic Bypass Option: bypass, input, and output contactors. Each circuit includes
a NO relay. Controller board connector J7 enables circuit connections. The relay
circuits route power to the SED2 and the motor via the contactors. Controlling the
contactors through the relay circuits is the main function of the Controller board.

Bypass Contactor

– The bypass relay on the Controller board controls the bypass

contactor. The output and bypass relays are interconnected to 120 Vac Hot. This
enables a safety circuit that prevents the bypass and output contactors from
simultaneously being energized.

Output Contactor

– The output relay on the Controller board controls the output

contactor.

Input Contactor

– The input relay on the Controller board controls the optional input

contactor.

Keypad Functions

Bypass

STOP

RESET

Enable

Input

Contactor

Output

Contactor

Bypass

Contactor

Overload

Relay

VFD

Hand

Start

Remote

Start

INTERLOCK START LOGIC

Enable Commanded Proofed

Auto Bypass Enabled

Essential Services

VFD Fault

Safety Fault

Overload Fault

Motor

VFD0096R1

2-CONTACTOR KEYPAD

VFD

Bypass

STOP

RESET

Input

On/Off

Enable

Input

Contactor

Output

Contactor

Bypass

Contactor

Overload

Relay

VFD

Hand

Start

Remote

Start

INTERLOCK START LOGIC

Enable Commanded Proofed

Auto Bypass Enabled

Essential Services

VFD Fault

Safety Fault

Overload Fault

Motor

VFD0097R1

3-CONTACTOR KEYPAD

Figure 4. E-Bypass Keypad Indicators and Pushbuttons.

The keypad provides user interface indicators and pushbuttons. The following table
describes specific pushbutton and indicator functions: