Application Feature Setup

Overview

The Controller board supports six
isolated digital inputs and six digital relay
outputs for customer use (Figure 13).
The digital inputs include: Remote Start
Input, Remote Safety #1 and #2,
Interlock Start, Essential Services, and
Overload Trigger. The digital outputs
include:

• VFD

Fault

• Programmable

Output

• Drive

Select

• Bypass

Select

• Bypass

Running

• Overload

Fault

Programmable Output, NO

COM

NC

VFD Fault, NO

COM

NC

Drive Select, COM

NO

Bypass Select, COM

NO

Bypass Running, COM

NO

Overload Fault, COM

NO

DIGITAL

OUTPUTS

DIGITAL

INPUTS

J2

J1

13

14

15

16

17

18

19

20

21

22

23

24

25

26

1

2

3

4

5

6

7

8

9

10

11

12

Remote Start Input

Remote Safety #1

Remote Safety #2

Interlock Start

Essential Services

Overload Trigger

VFD0114R2

Figure 13. Controller Board Digital Inputs and Outputs.

Auto Bypass without Interlock

Description

The Auto Bypass feature enables the SED2 to initiate automatic bypass mode
operation. Closing of the SED2 Relay sends the motor to hand bypass mode. See
the SED2 VFD Startup, Operation, and Maintenance Manual (125-3201) for
programming of this relay and for its desired action.

When the SED2 initiates bypass mode operation, the following occurs:

• The SED2 stops delivering power

• The output contactor opens.

• The bypass contactor closes and the Programmable Output on the Controller

board closes.