Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page 33

Advertising
background image

Startup Procedures

Siemens Building Technologies, Inc.

25

Parameter Description

Action

Setting/

Default

P0310*

Rated Motor Frequency

12 Hz to 650 Hz

Rated motor frequency (Hz) from
motor nameplate.

Pole pair number is recalculated
automatically if the parameter is
changed.

1. Press to advance to

parameter P0310.

2. Press to access the

parameter values level.

3. Press to advance to

nominal frequency (60 Hz).

4. Press to confirm and save

the setting.

Setting =
Motor
nameplate 60
Hz

Default =
50 Hz/60 Hz

Default is
dependent on
the setting of
the motor
frequency and
unit of
measurement
DIP switches.

P0311*

Rated Motor Speed

0 to 40,000 1/min

Rated motor speed (rpm) from
motor nameplate.

A setting of 0 causes an internal
calculation of this value.

Vector control and V/f control
with speed controller require this
value.

Slip compensation in V/f control
requires this value for correct
operation.

Pole pair number is recalculated
automatically if the parameter is
changed.

1. Press to advance to

parameter P0311.

2. Press to access the

parameter values level.

3 Press to advance to

nominal motor speed.

4. Press to confirm and save

the setting.

Setting =
Motor
nameplate

Default =
Varies by
model

* Motor related parameters.