SED2 VFD Electronic Bypass Option Operating Instructions

18

Siemens Building Technologies, Inc.

Table 4. Wire Sizes and Tightening Torques for E-Bypass with 500V to 600V Drive.

Circuit Breaker

Disconnect

Switch

Overload Ground

Lug

Part

Number

Bypass

Frame

Size

HP kW Amps

Wire

Size *

Torque,

lb-in

(Nm)

Wire

Size *

Torque,

lb-in

(Nm)

Wire

Size *

Torque,

lb-in

(Nm)

Range,

Amps

Max

Backup

Fuse,

Amps

Wire

Size*

Torque,

lb-in

(Nm)

VBE40.5---- C 0.5

0.37

.9

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

.7 - 1.0

4

14-2

35 (4)

VBE40.7---- C 0.7

0.55

1.3

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

.9 - 1.25

5

14-2

35 (4)

VBE41.0---- C 1.0

0.75

1.4

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

1.1 - 1.6

6

14-2

35 (4)

VBE41.5---- C 1.5

1.1

2.1

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

1.8 - 2.5

10

14-2

35 (4)

VBE42.0---- C 2.0

1.5

2.7

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

2.2 - 3.2

12

14-2

35 (4)

VBE43.0---- C 3.0

2.2

3.9

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

2.8 - 4

16

14-2

35 (4)

VBE45.0---- C 5.0

4.0

6.1

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

4.5 - 6.3

25

14-2

35 (4)

VBE47.5---- C 7.5

5.5 9

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

7 - 10

40

14-2

35 (4)

VBE410.---- C 10

7.5

11

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

9 - 2

45

14-2

35 (4)

VBE415.---- C 15

11.0

17

14-10

Cu

32 (3.6)

14-8

17 - 22

(1.9 - 2.5)

14-10

18 - 22

(2 - 2.5)

14 - 20

80

14-2

35 (4)

VBE420.---- C 20

15.0

22

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-8

17 - 22

(1.9 - 2.5)

14-10

18 - 22

(2 - 2.5)

17 - 22

80

14-2

35 (4)

VBE425.---- C 25

18.5

27

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-6

22 - 27

(2.5 - 3.1)

18-3

27 - 40

(3.1 - 4.5)

22 - 32

125

14-2

35 (4)

VBE430.---- D 30

22.0

32

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-6

22 - 27

(2.5 - 3.1)

18-3

27 - 40

(3.1 - 4.5)

28 - 40

150

14-2

35 (4)

VBE440.---- D 40

30.0

41

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-6

22 - 27

(2.5 - 3.1)

18-3

27 - 40

(3.1 - 4.5)

36 - 45

175

14-2

35 (4)

VBE450.---- E 50

37.0

52

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-6

22 - 27

(2.5 - 3.1)

18-3

27 - 40

(3.1 - 4.5)

40 - 50

200

14-2

35 (4)

VBE460.---- E 60

45.0

62

10-1/0

Cu

20 - 60

(2.2 - 6.8)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

45 - 63

250

14-2

35 (4)

VBE475.---- F 75

55.0

77

3-3/0

Cu

80 (9)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

70 - 90

350

14-2/0

50 (5.6)

VBE4100---- F 100

75.0

99

3-3/0

Cu

80 (9)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

80 - 100

400

14-2/0

50 (5.6)

VBE4125---- F 125

90.0

125

6 - 350

kcmil

Cu

120 - 275

(14 - 31.1)

6 - 350

kcmil

120 - 275

(14 - 31.1)

10-1/0

124 - 210

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

* Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum
600 Vac.