Installation instructions, Siemens building technologies, inc. 13, Figure 9. e-bypass power circuit – Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page 21

Advertising
background image

Installation Instructions

Siemens Building Technologies, Inc.

13

GND

GND
LUG

M1

(5)

(6)

(T1)

OL1

1T1

1T2

(T2)

(T3)

1T3

M

(1)

(2)

M2

(1) (2)

A2

B2

U

V

(3)

(5) (6)

(4)

C2

W

(3)

(4)

2L1

2L2

A1

B1

U1

V1

U

VFD

L1

C1

W1

W

L3

GND

L2

V

R

S

B2

A2

2L3

A1

B1

3L1

3L2

T

C2

C1

3L3

FU1

1L1

1L2

(L1)

L1

L2

(T1)

DISC1

M3

(2)

(4)

(6)

1L3

(L3)

L3

(T3)

GND

(L2)

(T2)

1L1

1L2

(5)

(3)

(1)

OPTIONAL SUPPLEMENTARY

POWER FUSES - MAIN SHORT

CIRCUIT PROTECTION BY OTHERS

(SEE NOTE 1)

OPTIONAL

DRIVE INPUT
CONTACTOR

OPTIONAL

INPUT LINE

REACTOR

OPTIONAL

OUTPUT LOAD

REACTOR

AC MOTOR
(CUSTOMER
SUPPLIED)

GND
LUG

POWER
SUPPLY
3 PHASE
60 Hz

TO

STEP-DOWN

CONTROL

TRANSFORMER

VFD0160R1

NOTES:

1. Branch circuit protection to be provided by installer, per UL508A, if not provided with drive.

2. For bypass operation, modify these drive parameters: P0702[0] and P0702[1] = 3,

P0748 = Digital Out 1 Reverse (

).

3. Control and communication wiring should be 300V UL minimum.

4. Communication wiring should be run with maximum separation possible from all other

wiring.

5. Essential service mode operates the motor full speed (bypass) with no protection for the

motor or system.

6. Ensure that automatic bypass will not damage the system before activating.

7. See Table 8 for proper fuse and wire sizes.

8. See Siemens Publication No. 125-3201 for SED2 input/output control signal wiring details.

Figure 9. E-Bypass Power Circuit.