SED2 VFD Electronic Bypass Option Operating Instructions

26

Siemens Building Technologies, Inc.

Parameter Description

Action

Setting/

Default

P0640

Motor Overload Factor

10% to 400%

Limited to the maximum SED2
output current rating, or to 400%
of the rated current (P0305),
whichever is lower.

NOTE:
This parameter is available when
P0003 = 3 and
P0010 = 1.

1. Press to advance to

parameter P0640.

2. Press to access the

parameter values level.

3. Press to advance to

desired value.

4. Press to confirm and save

the setting.

Setting =
As applicable

Default = 110

P0700(0)**

Selection of Command Source
(Start Command)

Selects the command source as
follows:

0 = Factory default setting

1 = BOP (keypad)

2 = Terminal digital input

4 = USS on BOP link (AOP)

5 = USS on COM link

6 = CB (Communications board
or module) on COM link (P1/N2)

1. Press to advance to

parameter P0700.

2. Press

to access the

parameter indexes.

3. Press to advance to index

[0], IN000, AUTO.

4. Press to confirm index

selection.

5. Press to advance to 2.

6. Press to confirm and save

the setting.

Setting = 2

Default = 2

NOTE:

Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.

** Parameters have two index settings: IN000 = Auto and IN001 = Hand.