SED2 VFD Electronic Bypass Option Operating Instructions

22

Siemens Building Technologies, Inc.

Parameter Description

Action

Setting/

Default

P0003

User Access Level

Allows you to access more
parameters.

1 = Standard

2 = Extended

3 = Expert

1. Press to access parameter

r0000 and to enter the SED2
parameter mode.

2. Press to advance to

parameter P0003.

3. Press to access the

parameter values level.

4. Press to advance to 3

(expert level).

5. Press to confirm and save

the P0003 = 3 setting.

Setting = 3

Default = 1

NOTE:

Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available
during quick commissioning.

P0010

Quick Commissioning

0 = Ready to Run

1 = Quick Commissioning

30 = Factory Setting

1. Press to access parameter

r0000 and to enter the SED2
parameter mode.

2. Repeatedly

press to

advance to parameter P0010.

3. Press to access the

parameter values level.

4. Press to advance to 1.

5. Press to confirm and save

the P0010 = 1 setting.

Setting = 1

Default = 0

NOTES:

1. P0010 must always be set back to 0 before operating the motor.

2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.