Application Feature Setup

Siemens Building Technologies, Inc.

43

NOTES:

1. All safety conditions must be met for bypass mode operation.

2. The input contactor remains energized.

The Electronic Bypass Option will return to VFD mode operation as soon as the
SED2 Relay in control opens. When the Electronic Bypass Option returns to VFD
mode operation, the following occurs:

• The SED2 Relay opens, the Programmable Output on the Controller

board opens, and the bypass contactor opens.

• The output contactor closes.

NOTE:

All safety conditions must be met for VFD mode operation.

Settings

The Auto Bypass feature requires that Controller board
DIP Switch 2 is set ON.

NOTE:

During operation, the Auto Bypass Enabled
indicator is on steady.

ON

12

5

34

12

5

34

ON

OFF

SW1

VFD0117R1

Example SED2 Settings

Set parameters P0732 and P0748 for Auto Bypass on Drive Fault. Programming of
the SED2 Relay is required for proper Auto Bypass activation. Set P0732 and P0748
as follows:

Parameter Setting

P0732 in000

52.3

P0732 in001

52.3

P0748