SED2 VFD Electronic Bypass Option Operating Instructions

32

Siemens Building Technologies, Inc.

Parameter Description

Action

Setting/

Default

P1202

Motor Current: Flying Start

Defines search current used for
flying start. Value is in % based
on the rated motor current
(P0305).

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1202.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 10
Default = 100
Maximum =
200

NOTE:

Reducing the search current may improve performance for flying start if the inertia of the system is not very
high.

P1203

Search Rate: Flying Start

Sets factor by which the output
frequency changes during flying
start to synchronize with the
turning motor. This value,
entered in % relative to the
default time factor, defines the
initial gradient and influences the
time taken to search for the
motor frequency.

The search time is the time taken
to search through all frequencies
between
f_max + 2 × f_slip to 0 Hz.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1203.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 10
Default = 100
Maximum =
200

NOTES:

1. P1203 = 100% is defined as giving a rate of 2% of f_slip, nom/ms.

2. P1203 = 200% would result in a rate of frequency change of 1% of f_slip, nom/ms.

3. A higher value produces a flatter gradient, and thus a longer search time. A lower value has the

opposite effect.