SED2 VFD Electronic Bypass Option Operating Instructions

40

Siemens Building Technologies, Inc.

Reset to Factory Defaults

Parameter Description

Action

Setting/

Default

P0010
P0970

Reset to Factory Default

Resets SED2 parameters to the
factory defaults.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P0010.

3. Press to access the

parameter values level.

4. Press to advance to 30.

5. Press to confirm and save

the setting.

6. Press to go to parameter

P0970

.

7. Press to access the

parameter values level.

8. Press to advance to 1.

9. Press to confirm and save

the setting.

P0010:
Setting = 30
Default = 0

P0970:
Setting = 1
Default = 0

NOTES:

1. First set P0010 = 30.

2. Stop SED2 (that is, disable all pulses) before you reset parameters to factory default values.

3. The following parameters retain their values after a factory reset:

P0918 (address of CB, communications board or module)

P2010 (USS baud rate)

P2011 (USS address)

4. The reset process takes about 10 seconds.