Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page 31

Advertising
background image

Startup Procedures

Siemens Building Technologies, Inc.

23

Parameter Description

Action

Setting/

Default

P0100

Operation for Europe/N.
America

0 = 50 Hz, kW (Europe)
factory

default

1 = 60 Hz, hp
(North

America)

2 = 60 Hz, kW
(North

America)

The setting of Motor Frequency
and Unit of Measurement DIP
switch 2 overrides P0100
settings 0 and 1.

1. Press to advance to

parameter P0100.

2 Press to access the

parameter values level.

3. Press to advance to 1.

4. Press to confirm and save

the P0100 = 1 setting.

Setting = 1

Default = 0 or
1

(Default is
determined by
the setting of
the motor
frequency and
unit of
measurement
DIP switches.)

NOTES:

1. Stop the SED2 (that is, disable all pulses) before changing this parameter.

2. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the

rated motor parameters (such as P0340, Calculation of motor Parameters).

P0304*

Rated Motor Voltage

10V to 2000V.

Rated motor voltage (V) from
motor nameplate.

1. Press to advance to

parameter P0304.

2. Press to access the

parameter values level.

3. Press to advance to

nominal voltage.

4. Press to confirm and save

the setting.

Setting =
Motor
nameplate

Default =
Varies by
model

* Motor related parameters.