Troubleshooting

Siemens Building Technologies, Inc.

51

Troubleshooting

WARNING:

Always disconnect all power sources before opening the SED2 Electronic
Bypass Option.

Power-on Initialization Failure
(Unit Fault Condition)

During power-on initialization, a unit fault condition occurs if the Electronic Bypass
Option did not pass the basic sanity test. Rather than flash normally, the basic sanity
test indicator pauses, flashes a fault code, and then repeats.

Table 7 shows the fault codes. For example, if the basic sanity test indicator flashes
three times rapidly, pauses, and then repeats, this means that there is a keypad
failure.

Table 7. Basic Sanity Test Fault Codes.

Basic Sanity

Test Fault

Code/Flashes

Description

1

Non-Volatile Memory Failure

2

Flash Memory Failure (CRC, cyclic redundancy check)

3 Keypad

Failure

4

RAM Memory Failure (not used)

5

EEPROM Read error

6

EEPROM Write Failure

7

Runtime Flash Failure (CRC, cyclic redundancy check)

8

Main Program Failed (or hangs)

It may be possible to recover from the unit fault condition by simply attempting a
power down/up of the Electronic Bypass Option. If the unit fault condition still exists,
replace the Controller board.

CAUTION:

When powering down/up the Electronic Bypass Option, power down the unit,
wait 5 minutes, and then power up the unit.