Pulse frequency – Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page 45

Advertising
background image

Startup Procedures

Siemens Building Technologies, Inc.

37

Pulse Frequency

Parameter Description

Action

Setting/

Default

P1800

Pulse Frequency

Sets pulse frequency (kHz) of
power switches in SED2. The
frequency can be changed in
increments of 2 kHz.

Pulse frequencies > 4 kHz
selected on 380V to 480V units
reduce the maximum continuous
motor current.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1800.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 4

Default =
Varies by
model
(hp/voltage
dependent)

Maximum = 16

NOTES:

1. Minimum pulse frequency depends on P1082 (maximum frequency) and P0310 (rated motor

frequency).

2. At 4 kHz, full output current is obtained up to 50 degrees C (CT mode); over 50 degrees C, full output

may be obtained at 8 kHz.

3. If silent operation is not absolutely necessary, lower pulse frequencies may be selected to reduce SED2

losses and radio-frequency emissions.

4. Under certain circumstances, the SED2 may reduce the switching frequency to provide protection

against over-temperature.