Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual

Page 36

Advertising
background image

SED2 VFD Electronic Bypass Option Operating Instructions

28

Siemens Building Technologies, Inc.

Parameter Description

Action

Setting/

Default

P1000[1]**

Selection of Frequency
Setpoint

(Speed Command Source)

Selects the frequency setpoint
source as follows:

1 = Motor potentiometer
setpoint/AOP

2 = Analog input

3 = Fixed frequency

4 = USS on BOP Link/AOP

5 = USS on COM link

6 = CB (Communications board
or module) on COM link (P1/N2)

1. Press to advance to index

[1], IN001, HAND.

2. Press to confirm index

selection.

3. Press to advance to 1.

4. Press to confirm and save

the setting.

5. Press again to return to the

parameter selection level.

Setting = 1

Default = 1

P1080

Minimum Motor Frequency

0 Hz to 650 Hz

Minimum motor frequency at
which the motor will run
irrespective of the frequency
setpoint. This value applies to
both clockwise and
counterclockwise rotation.

1. Press to advance to

parameter P1080.

2. Press to access the

parameter values level.

3. Press to advance to

desired value.

4. Press to confirm and save

the setting.

Site Setting

(20% to 30%
Max)

Default = 10

** Parameters have two index settings: IN000 = Auto and IN001 = Hand.