Additional Parameter Settings

NOTE:

If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP

display alternately shows setpoint values and the actual value (0 Hz).

Flying Start

Parameter Description

Action

Setting/

Default

P1200

Flying Start

Starts SED2 into a spinning
motor by rapidly changing the
output frequency of the SED2
until the actual motor speed is
found. Then, the motor runs up
to setpoint using the normal
ramp time.

0 = Flying start disabled.
1 = Flying start is always active,
start in direction of setpoint.
2 = Flying start is active, if power
on, fault, OFF2, start in direction
of setpoint.
3 = Flying start is active if fault,
OFF2, start in direction of
setpoint.
4 = Flying start is always active,
only in direction of setpoint.
5 = Flying start is active if power
on, fault, OFF2, only in direction
of setpoint.
6 = Flying start is active if fault,
OFF2, only in direction of
setpoint.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1200.

3. Press to access the

parameter values level.

4. Press to advance to

desired setting.

5. Press to confirm and save

the setting.

Minimum = 0

Default = 0

Maximum = 6

Suggested = 2

NOTES:

1. Flying start is useful for motors with high inertia loads.

2. Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the

setpoint.

3. Flying start must be used in cases where the motor may still be turning (such as after a brief input

power break) or can be driven by the load. Otherwise, overcurrent trips occur.

4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by

reducing the values in P1203 and P1202.