Interlock and Auto Bypass on VFD Fault

Description

Interlock and Auto Bypass features are both active. Auto bypass now becomes auto
bypass on a VFD fault only (bypass is initiated by the SED2 Fault and this digital
output must always be programmed to VFD fault).

• All set-up is the same as with Interlock (see the Interlock section in

Application Feature Setup).

• Hand bypass is now initiated by SED2 Fault.

• The Programmable Output is still used to initiate the proofing sequence.

Settings

Interlock and Auto Bypass requires that Controller
board DIP Switches 2 and 3 are set ON.

NOTE:

During operation, the Auto Bypass Enabled
indicator is on steady. Also, the Interlock
Start Logic Enabled indicator is on steady.

ON

12

5

34

12

5

34

ON

OFF

SW1

VFD0120R1

See the Auto Bypass without Interlock on VFD Relay Output and Interlock sections
for parameter settings.

Wiring Example for
Interlock and Auto
Bypass on VFD Fault

Customer

Proof

Power to

Customer

Device

Programmable Output, NO

COM

NC

DIGITAL OUTPUTS

DIGITAL INPUTS

J2

J1

13

14

15

16

17

18

19

20

21

22

23

24

25

26

1

2

3

4

5

6

7

8

9

10

11

12

Remote Start Input

Remote Safety #1

Remote Safety #2

Interlock Start

VFD0115R2