Startup Procedures

Siemens Building Technologies, Inc.

35

Parameter Description

Action

Setting/

Default

P1211

Number of Restart Attempts

Specifies the number of times
SED2 will attempt to restart after
supply power brownout or fault, if
P1210 automatic restart is
activated.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1211.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 0
Default = 3
Maximum = 10

Suggested =
10

P1212

Time to First Restart

Selects the time (seconds)
before the SED2 is restarted for
the first time if P1210 automatic
restart is activated.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1212.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 0
Default = 3
Maximum = 10

Suggested =
10