SED2 VFD Electronic Bypass Option Operating Instructions

36

Siemens Building Technologies, Inc.

Parameter Description

Action

Setting/

Default

P1213

Restart Time Increment

Selects the amount (seconds)
that the restart time is
incremented for each restart of
the SED2 if P1210 automatic
restart is activated.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1213.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 0
Default = 30
Maximum =
1000

Suggested =
10

Vdc Controller

Parameter Description

Action

Setting/

Default

P1240

Configuration of Vdc
Controller

Enables/disabled Vdc controller.

The Vdc controller dynamically
controls the DC link voltage to
prevent overvoltage trips on high
inertia systems.

Vdc-max automatically increases
ramp-down times to keep the DC
link voltage (r0026) within limits.

0 = Vdc controller disabled
1 = Vdc-max controller enabled
2 = Reserved
3 = Reserved

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1240.

3. Press to access the

parameter values level.

4. Press to advance to

desired value.

5. Press to confirm and save

the setting.

Minimum = 0
Default = 1
Maximum = 3