SED2 VFD Electronic Bypass Option Operating Instructions

46

Siemens Building Technologies, Inc.

Wiring Example for Interlock

Customer

Proof

Power to

Customer

Device

Programmable Output, NO

COM

NC

DIGITAL OUTPUTS

DIGITAL INPUTS

J2

J1

13

14

15

16

17

18

19

20

21

22

23

24

25

26

1

2

3

4

5

6

7

8

9

10

11

12

Remote Start Input

Remote Safety #1

Remote Safety #2

Interlock Start

VFD0115R2

Essential Services

Description

The Essential Services feature allows full-power bypass mode control of the motor
during an emergency scenario. Activation of Essential Services overrides any other
selected operation. Essential Services ensures that the bypass contactor will not
open when a safety input or overload opens. Power goes directly to the motor.

NOTES:

1. If using both the Interlock and Essential Services features, Essential Services

waits 10 seconds for the Interlock to confirm the safety condition (such as
opening a damper). After the 10-second delay, Essential Services controls the
motor regardless of the Interlock safety condition status.

2. Use extreme care when using the Essential Services mode. All safety circuits are

no longer active (including motor overload and safety inputs to the Controller
board).