52

Siemens Building Technologies, Inc.

Override Jumper

An Override Jumper (J8) is supplied
on the Controller board. Moving this
jumper to the override position
removes the Controller board and its
keypad from the control and closes the
drive output contactor (and the input
contactor if supplied).

Fuses

J2

J8

J1

BPEC

OVERRIDE JUMPER
J8 SHOWN IN
OVERRIDE POSITION

J2

J8

J1

BPEC

OVERRIDE JUMPER
J8 SHOWN IN
NORMAL POSITION

VFD0121R1

Figure 14. Override Jumper J8 Location and Positions.

The Controller board contains a fuse (F1) under its cover (Figure 15). Determine if
the fuse F1 needs replacement as follows:

1. If the basic sanity test indicator (Figure 15) is flashing, fuse F1 is OK and no

action is required.

2. Verify that 120 Vac power is available on the secondary side of the Electronic

Bypass Option power transformer (Figure 15). If power is not proper, check the
Electronic Bypass Option components such as:

• Power

transformer

• Power transformer fuses (F2, F3, and F4). Table 8 provides fuse

replacement information.

3. If power is proper, check fuse F1 as follows:

• Power down the Electronic Bypass Option.

• Remove the Controller board cover.

• Remove fuse F1.

• Use an ohm meter to check the fuse.

• Replace fuse F1 if necessary.

NOTE:

Replace fuse F1 with an 8 AG, 1/2 amp, 250V, fast-acting instrument fuse
such as a Bussmann AGX1/2 or Littlefuse 361.500.

Advertising