Gram shown in figure a.2, Installation – Lincoln Electric COMMANDER SVM153-A User Manual

Page 14

Advertising
background image

1. Install the double-pole, double-throw switch

between the power company meter and the
premises disconnect.

Switch rating must be the same or greater than the cus-
tomer’s premises disconnect and service over current
protection.

2. Take necessary steps to assure load is limited to

the capacity of the Commander by installing a 50
amp, 240 VAC double-pole circuit breaker.
Maximum rated load for each leg of the 240 VAC
auxiliary is 50 amperes. Loading above the rated
output will reduce output voltage below the allow-

able -10% of rated voltage, which may damage
appliances or other motor-driven equipment and
may result in overheating of the Commander 500
engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type

14-50) to the double-pole circuit breaker using No.
6, four-conductor cable of the desired length. (The
50 amp, 120/240 VAC plug is available in the
optional K802R plug kit.)

4. Plug this cable into the 50 amp 120/240 volt recep-

tacle on the Commander 500 case front.

A-8

A-8

INSTALLATION

COMMANDER 500

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

FIGURE A.2 – CONNECTION OF THE COMMANDER 500 TO PREMISES WIRING

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE. SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE