PRODUCT SPECIFICATIONS

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

14-2

14.3

UPS System Output

DC Filtering

Ripple voltage less than 0.5% peak to peak

UPS Output Capacity

100% rated current at 0.8 power factor or 100% rated current at 0.9 power
factor

Output Voltage Regulation

1% (10% to 100% load)

Output Voltage
Adjustment
(Nominal +/–5%)

600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)
480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)
400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)

Output Voltage Harmonic
Content

3% max THD, 2% max single (linear load)

Output Voltage Balance

3% for 100% maximum load imbalance (linear load)

Output Voltage Phase
Displacement

3° for 100% maximum load imbalance (linear load)

Output Transients

"5% for 100% load step or removal

Frequency Regulation

"0.01 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass within
"0.5 Hz

Frequency Slew Rate

1 Hz per second maximum (adjustable)

Overload Capability

125% for 10 minutes
150% for 10 seconds

Maximum Output
Capability

300% peak for 10 cycles without bypass

14.4

Environmental Specifications

Operating Temperature

0 to 40°C (32–104°F) without derating. The recommended operating
temperature is 25°C (77°F).

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

Storage Temperature

–20 to +70°C (prolonged storage above 40°C will cause rapid battery
self‐discharge)

Relative Humidity
(Operating and Storage)

95% maximum noncondensing

Acoustical Noise

75 dBA at a 1m distance

Electrostatic Discharge
(ESD) Immunity

Meets IEC 801‐2 specifications.