Powerware 9315 User Manual

Page 142

Advertising
background image

INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-32

Table P. Output/Inverter Cabinet Customer Interface Connections

CUSTJ4 Terminal

Name

Description

1

Building Alarm 2

Programmable UPS alarm. Activated by a remote dry contact closure.

2

Building Alarm 2 Return

3

Building Alarm 3

Programmable UPS alarm. Activated by a remote dry contact closure.

4

Building Alarm 3 Return

5

Building Alarm 4

Programmable UPS alarm. Activated by a remote dry contact closure.

6

Building Alarm 4 Return

7

Building Alarm 5

Programmable UPS alarm. Activated by a remote dry contact closure.

8

Building Alarm 5 Return

9

Not Used

10

Not Used

CUSTJ2 Terminal

Name

Description

1

Relay 1 NC

General purpose normally‐open and normally‐closed relay contacts.

2

Relay 1 Commom

3

Relay 1 NO

4

Building Alarm 1

Programmable UPS alarm. Activated by a remote dry contact closure.

5

Building Alarm 1 Return

6

Relay 2 NC

General purpose normally‐open and normally‐closed relay contacts.

7

Relay 2 Common

8

Relay 2 NO

9

Not Used

10

Not Used

CUSTTB Terminal

Name

Description

1

CB3 - Aux #2

Circuit breaker CB3 auxiliary contact.

2

CB3 - Aux #2*

3

Not Used

4

Remote to Bypass

Dry contact used to activate remote transfer to bypass.

5

Remote to Bypass Return

6

Remote to UPS

Dry contact used to activate remote transfer to UPS.

7

Remote to UPS Return

8

Not Used

9

REPO

Dry contact used to activate REPO of UPS.

10

REPO Common

Advertising