INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-14

Table F. Input/Output Ratings and External Wiring Requirements (PW9315-700/500 and PW9315-750/562)

Basic Unit Rating

PW9315-750/500 at 0.8 Lagging pF Load
PW9315-750/562 at 0.9 Lagging pF Load

Units

Rating 50/60 Hz

kVA/kW

625/500

625/500

625/562

625/562

Input and Output Voltage

Volts

480

600

480

600

AC Input to UPS Rectifier (0.95 Min. pF)

(3) Phases, (1) Neutral, (1) Ground

A

Amps*

951

761

984

787

Minimum Conductor Size
Number per Phase
* Maximum amps includes full load current plus
battery recharge current

AWG or kcmil

(each)

400

(4)

350

(4)

500

(4)

350

(4)

AC Input to MBC (UPS Bypass)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

DC Input from Battery to UPS

(1) Positive, (1) Negative

C

Vdc

Amps @ (2.0V/cell)

384

1370

384

1370

384

1542

384

1542

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

500

(6)

500

(6)

600

(6)

600

(6)

AC Output to Optional SBM

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

E

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

752

601

752

601

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(3)

350

(3)

NOTE

Callout letters A, B, C, D, and E map to Figure A‐8.