INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-36

NOTE The Summary Alarm Relay contact rating is 32 Vac/42 Vdc maximum switched voltage and 1A
maximum current.

NOTE Relays are shown in de‐energized state. Relays change state when an UPS alarm event occurs.

8

7

6

RELAY 2

3

2

1

RELAY 1

Figure A‐23. Summary Alarm Relay Contacts

A.6

Typical REPO

The REPO feature opens all contactors in the UPS cabinet and isolates power from
your critical load. Local electrical codes may also require tripping upstream
protective devices to the UPS.

NOTE REPO switch rating is 6A/120 Vac or 3A/240 Vac. The REPO switch must be a latching-type
switch with a dedicated circuit.

REPO

Switch

Twisted

Wires (2)

CUSTTB

10

9

Figure A‐24. REPO Wiring