INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-20

Table L. Maximum Output Circuit Breaker Ratings

UPS Model

Output Voltage Rating

400V

480V

600V

PW9315-625/400
PW9315-625/450

800A

N/A

N/A

PW9315-625/500
PW9315-625/562

1000A

N/A

N/A

PW9315-750/500
PW9315-750/562

N/A

800A

700A

PW9315-750/600
PW9315-750/675

N/A

1000A

800A

21. DC input overcurrent protection and disconnect switch are to be provided by

the user. Table M lists the maximum rating for continuous duty rated circuit
breakers satisfying the criteria for both.

Table M. Maximum DC Input Circuit Breaker Ratings

UPS Model

Output Voltage Rating

400V

480V

600V

PW9315-625/400
PW9315-625/450

1600A

N/A

N/A

PW9315-625/500
PW9315-625/562

1800A
2000A

N/A

N/A

PW9315-750/500
PW9315-750/562

N/A

1800A
2000A

1800A
2000A

PW9315-750/600
PW9315-750/675

N/A

2000A
2300A

2000A
2300A

22. Table N lists the battery shunt trip trip wiring requirements.

Table N. Battery Shunt Trip Wiring Requirements

Description

ST

CB2TB Points

9, 10

Output Max Pulse

220 VA instantaneous

Wiring

#18 AWG minimum

23. There is no DC disconnect device within the UPS.

24. The DC input to the UPS is protected by internal fuses F30 and F31.

25. Recommended wire size is #18–14 AWG.

26. Battery voltage is computed at 2 volts per cell as defined by Article 480 of the

NEC. Rated battery current is computed at 2 volts per cell.

27. The battery wiring used between the battery and the UPS should not allow a

voltage drop of more than 1% of nominal DC voltage at rated battery current.