INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201244 Rev E www.powerware.com

A-33

NOTE All building alarm inputs or remote features require an isolated normally-open contact or switch (rated at
24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. All control wiring and
relay and switch contacts are customer-provided.

NOTE Regardless of how you assign the building alarms, the default is to display the alarms as Building Alarm 1,
Building Alarm 2, and so on, on the monitor panel. Use twisted-pair wires for each alarm input and common.

1

10

CUSTJ4

CUSTJ2

1

10

10

1

RELAY #1 NC

RELAY #1 COMMON

RELAY #1 NO

RELAY #2 NC

RELAY #2 COMMON

RELAY #2 NO

BUILDING ALARM #2

BUILDING ALARM #2-RETURN

BUILDING ALARM #3

BUILDING ALARM #3-RETURN

BUILDING ALARM #4

BUILDING ALARM #4-RETURN

BUILDING ALARM #5

BUILDING ALARM #5-RETURN

REPO

REPO COMMON

REMOTE TO UPS RETURN

REMOTE TO UPS

REMOTE TO BYPASS RETURN

REMOTE TO BYPASS

CB3-AUX #2*

CB3-AUX #2

INVERTER I/O BOARD

(USED ONLY IN MULTI-MODULE
APPLICATIONS USING AN SBM)

BUILDING ALARM #1

BUILDING ALARM #1 RETURN

Figure A‐21. Output/Inverter Cabinet – PCM 2 Customer Interface Wiring